ACB (MAINTENANCE, TROUBLE SHOOTING TESTING OF RELEASES)

 

AIR CIRCUIT BREAKERS



COMPLAINT :- BREAKER IS NOT CLOSING

 

PROBABLE CAUSE

a) Undervoltage release not connected with supply.

b) Undervoltage release, Shunt release,

 Magneto thermal release connecting link not adjusted properly.    

c) Magneto thermal release removed

from ACB, but trip bar of release

kept free. 

d) Latch of the mechanism spring not

in proper position or misplaced.

e) Under voltage release coil burnt

out or open circuited.

f ) Bimetal element of magneto

thermal release bent permanently.

g) After overload or short circuit fault,

breaker not reset (ONLY FOR

MANUALLY RESET TYPE ACB.)

h) Sticking of tripping mechanism due

to excess dust.

 

POSSIBLE SOLUTION


a) Give rated voltage to under

voltage release.

 

b) Adjust the connecting linkage

of releases correctly.

 

c) Lock the trip bar at given

position.

 

d) Fix the spring correctly.

 

e) Replace the under voltage

release.

 

f ) Replace the magneto thermal

release.

 

g) Reset the breaker by pressing

OFF / RESET button.

 

h) Clean the tripping mechanism

with CRC 2-26 & grease them,

(refer section on greasing)

 

 

COMPLAINT :- BREAKER IS NOT TRIPPING WITH UNDERVOLTAGE OR SHUNT RELEASE.

 

PROBABLE CAUSE

 

a) Shunt release does not get supply.

 

b) Supply of under voltage release

does not get cut off.

 

c) Link pins of Undervoltage or shunt

release misplaced.

 

d) Due to dust release becomes

sticky.

 


 

POSSIBLE SOLUTION

 

a) Check control wiring of shunt release & ensure that shunt release gets supply.

 

b) Check control wiring.

 

c) Ensure that pins are in

position.

 

d) Remove the dust from the

release & clean it with

CRC 2-26

 

COMPLAINT :- BREAKER IS NOT TRIPPING BY MANUAL TRIP PUSH BUTTON

 

PROBABLE CAUSE

 

a) Trip push buttons connecting

link is short. (Not adjusted

properly.)

 

b) Latch of the mechanism.

jammed because of dust.

POSSIBLE SOLUTION

a) Adjust the push button link

correctly.

 

b) Clean the latch of the mechanism

with CRC 2-26.

 

 

 

 








COMPLAINT :-  ACB IS NOT TRIPPING IN CASE OF OVERLOAD OR SHORT CIRCUIT FAULT

 

 

PROBABLE CAUSE

 

a) Connection between C.T. and

magneto thermal release is

loose or open circuit.

 

b) Overload setting of magneto

thermal release is more than

actual load current.

 

c) Magneto thermal release

linkage not adjusted properly.

 

POSSIBLE SOLUTION

 

a) Tighten the terminals of C.T. in

case of open circuit.

 

b) Make the overload setting of ACB

as per actual load current.

 

c) Connect the linkage of magneto

thermal release to trip bar properly

& ensure its tripping operation.

 

 

COMPLAINT :-  MAIN CONTACTS OF ONE OF THE POLE OF ACB NOT CLOSING

 

 

PROBABLE CAUSE

 

a) Excessive dust accumulated

in the pole assembly.

 

b) Nylon rollers of the pole

assembly are not rotating

smoothly.

 

c) Pole connector setting

disturbed.

 

d) Nylon rollers of the pole

assembly are broken

 

POSSIBLE SOLUTION

 

a) Clean the pole assembly mechanism with CRC 2-26. Remove grease and dust with

brush & apply fresh grease.

 

b) Clean the nylon rollers with CRC

2-26 and relubricate them.

(refer section on greasing)

 

c) Consult the manufacturer of Circuit

Breaker

 

d) Consult the manufacturer of Circuit

Breaker

COMPLAINT :-  PITTING ON MAIN CONTACTS

 

 

PROBABLE CAUSE

 

a) Arcing contact gap is not

adjusted properly.

 

b) Thickness of arcing contact is

reduced below the specified

limit. (> 0.5 mm)

 

POSSIBLE SOLUTION

 

a) Adjust the gap of arcing contacts,

it should be 0.9 + or -0.1 mm

 

b) Replace both fixed and moving

arcing contacts

 

COMPLAINT :-  EROSION ON ARCING CONTACTS

 

 

PROBABLE CAUSE

 

a) Rough deion plates of arc

chutes.

 

b) Breaker is operated without arc

chute in position

 

POSSIBLE SOLUTION

 

a) Clean the deion plates and side

insulating strips of arc chutes with

CRC2-26.

 

b) Always operate ACB with arc chute in

position & keep the arc chutes clean

 

 

COMPLAINT :-  BREAKER IS NOT RACKING IN THE CRADLE FREELY

 

 

PROBABLE CAUSE

 

a) Threads of mechanical

indicating assembly worn out.

 

b) Shutter assembly is not

properly set in the cradle.

 

c) Secondary isolating contacts

not matching properly.

 

d) Dovel pin broken.

 

e) Telescopic rail becomes

jammed.

 

POSSIBLE SOLUTION

 

a) Replace the mechanical indicating

assembly.

 

b) Fix the shutter assembly properly in

the cradle.

 

c) Match the fixed and moving

secondary isolation contacts properly.

 

d) Replace the dovel pin.

 

e) Clean the telescopic rail with CRC

2-26. Remove dust, grease &

relubricate it.



COMPLAINT :- OVERHEATING

 

 

PROBABLE CAUSE

 

a) Poor termination (High Milli-

Volt drop across termination

on ACB.)

 

b) Dusty atmosphere.

 

c) Use of undersized cable or

bus bars.

 

d) High ambient temperature

 

POSSIBLE SOLUTION

 

a) Clean the terminals with CRC 2-26

and do proper retermination. Ensure

that milli volt drop within specified

limits.

 

b) Do periodic cleaning of circuit breaker.

 

c) Use cables or bus bars of adequate

rating.

 

d) Reduce load current or select & install

correct rating of ACB

 

 

COMPLAINT :- BREAKER IS NOT CHARGING WITH MOTOR

 

 

PROBABLE CAUSE

 

a) Motor is not getting supply.

 

b) Loose connections in

secondary isolating contacts.

 

c) Motor is burnt out.

 

POSSIBLE SOLUTION

 

a) Check the limit switch of motor.

Replace it if it is damaged.

 

b) Fix the secondary isolating

contacts properly,

 

c) Replace the motor.

 

 

COMPLAINT :- BREAKER IS NOT CLOSING REMOTELY

 

 

PROBABLE CAUSE

 

a) Breaker is not in service

position

 

b) Closing coil is not getting

supply,

 

c) Closing coil burnt out or open

circuited.

 

POSSIBLE SOLUTION

 

a) Take the breaker in service

position.

 

b) Check control circuit and

ensure that coli gets supply.

 

c) Replace the closing coil,

 