AIR CIRCUIT BREAKERS
COMPLAINT :- BREAKER IS NOT CLOSING
PROBABLE CAUSE a) Undervoltage release not connected with supply. b)
Undervoltage release, Shunt release, Magneto thermal release connecting link not adjusted properly. c)
Magneto thermal release removed from
ACB, but trip bar of release kept free. d)
Latch of the mechanism spring not in proper position or misplaced. e) Under
voltage release coil burnt out or open circuited. f )
Bimetal element of magneto thermal release bent permanently. g)
After overload or short circuit fault, breaker
not reset (ONLY FOR MANUALLY RESET TYPE ACB.) h)
Sticking of tripping mechanism due to
excess dust. |
POSSIBLE SOLUTION a) Give rated voltage to under voltage release. b) Adjust the connecting linkage of releases correctly. c) Lock the trip bar at given position. d) Fix the spring correctly. e) Replace the under voltage release. f ) Replace the magneto thermal release. g) Reset the breaker by pressing OFF /
RESET button. h)
Clean the tripping mechanism with
CRC 2-26 & grease them, (refer section on greasing) |
COMPLAINT :- BREAKER IS NOT TRIPPING WITH UNDERVOLTAGE OR
SHUNT RELEASE.
PROBABLE CAUSE a)
Shunt release does not get supply. b)
Supply of under voltage release does
not get cut off. c)
Link pins of Undervoltage or shunt release
misplaced. d)
Due to dust release becomes sticky. |
POSSIBLE SOLUTION a)
Check control wiring of shunt release & ensure that shunt release gets
supply. b)
Check control wiring. c)
Ensure that pins are in position. d)
Remove the dust from the release
& clean it with CRC
2-26 |
COMPLAINT :- BREAKER
IS NOT TRIPPING BY MANUAL TRIP PUSH BUTTON
PROBABLE CAUSE a) Trip push buttons connecting link is short. (Not adjusted properly.) b) Latch of the mechanism. jammed because of dust. |
POSSIBLE SOLUTION a)
Adjust the push button link correctly. b)
Clean the latch of the mechanism with CRC 2-26. |
COMPLAINT :- ACB IS NOT TRIPPING IN CASE OF
OVERLOAD OR SHORT CIRCUIT FAULT
PROBABLE CAUSE a)
Connection between C.T. and magneto
thermal release is loose
or open circuit. b)
Overload setting of magneto thermal
release is more than actual
load current. c)
Magneto thermal release linkage
not adjusted properly. |
POSSIBLE SOLUTION a)
Tighten the terminals of C.T. in case
of open circuit. b)
Make the overload setting of ACB as
per actual load current. c)
Connect the linkage of magneto thermal
release to trip bar properly &
ensure its tripping operation. |
COMPLAINT :- MAIN CONTACTS OF ONE OF THE
POLE OF ACB NOT CLOSING
PROBABLE CAUSE a)
Excessive dust accumulated in
the pole assembly. b)
Nylon rollers of the pole assembly
are not rotating smoothly. c)
Pole connector setting disturbed. d)
Nylon rollers of the pole assembly
are broken |
POSSIBLE SOLUTION a)
Clean the pole assembly mechanism with CRC 2-26. Remove grease and dust with brush
& apply fresh grease. b)
Clean the nylon rollers with CRC 2-26
and relubricate them. (refer
section on greasing) c)
Consult the manufacturer of Circuit Breaker d)
Consult the manufacturer of Circuit Breaker |
COMPLAINT :- PITTING ON MAIN CONTACTS
PROBABLE CAUSE a)
Arcing contact gap is not adjusted
properly. b)
Thickness of arcing contact is reduced
below the specified limit.
(> 0.5 mm) |
POSSIBLE SOLUTION a)
Adjust the gap of arcing contacts, it
should be 0.9 + or -0.1 mm b)
Replace both fixed and moving arcing
contacts |
COMPLAINT :- EROSION ON ARCING CONTACTS
PROBABLE CAUSE a)
Rough deion plates of arc chutes. b)
Breaker is operated without arc chute
in position |
POSSIBLE SOLUTION a)
Clean the deion plates and side insulating
strips of arc chutes with CRC2-26. b)
Always operate ACB with arc chute in position
& keep the arc chutes clean |
COMPLAINT :- BREAKER IS NOT RACKING IN THE
CRADLE FREELY
PROBABLE CAUSE a)
Threads of mechanical indicating
assembly worn out. b)
Shutter assembly is not properly
set in the cradle. c)
Secondary isolating contacts not
matching properly. d)
Dovel pin broken. e)
Telescopic rail becomes jammed. |
POSSIBLE SOLUTION a)
Replace the mechanical indicating assembly. b)
Fix the shutter assembly properly in the
cradle. c)
Match the fixed and moving secondary
isolation contacts properly. d)
Replace the dovel pin. e)
Clean the telescopic rail with CRC 2-26.
Remove dust, grease & relubricate
it. |
COMPLAINT :- OVERHEATING
PROBABLE CAUSE a)
Poor termination (High Milli- Volt
drop across termination on
ACB.) b)
Dusty atmosphere. c)
Use of undersized cable or bus
bars. d)
High ambient temperature |
POSSIBLE SOLUTION a)
Clean the terminals with CRC 2-26 and
do proper retermination. Ensure that
milli volt drop within specified limits. b) Do
periodic cleaning of circuit breaker. c)
Use cables or bus bars of adequate rating. d)
Reduce load current or select & install correct
rating of ACB |
COMPLAINT :- BREAKER
IS NOT CHARGING WITH MOTOR
PROBABLE CAUSE a)
Motor is not getting supply. b)
Loose connections in secondary
isolating contacts. c)
Motor is burnt out. |
POSSIBLE SOLUTION a)
Check the limit switch of motor. Replace
it if it is damaged. b)
Fix the secondary isolating contacts
properly, c)
Replace the motor. |
COMPLAINT :- BREAKER
IS NOT CLOSING REMOTELY
PROBABLE CAUSE a)
Breaker is not in service position b)
Closing coil is not getting supply, c)
Closing coil burnt out or open circuited. |
POSSIBLE SOLUTION a)
Take the breaker in service position. b)
Check control circuit and ensure
that coli gets supply. c)
Replace the closing coil, |